<?xml version="1.0" encoding="UTF-8" standalone="yes"?>
<RSLogix5000Content SchemaRevision="1.0" SoftwareRevision="36.00" TargetName="AOI_PMM" TargetType="AddOnInstructionDefinition" TargetClass="Standard" TargetRevision="1.0 " TargetLastEdited="2025-07-18T14:50:08.259Z" ContainsContext="true" ExportDate="Wed Jul 30 11:54:15 2025" ExportOptions="References NoRawData L5KData DecoratedData Context Dependencies ForceProtectedEncoding AllProjDocTrans">
<Controller Use="Context" Name="MTN6_MCM01">
<DataTypes Use="Context">
<DataType Name="UDT_ALARMS_PMM" Family="NoFamily" Class="User">
<Members>
<Member Name="ZZZZZZZZZZUDT_ALARMS0" DataType="SINT" Dimension="0" Radix="Decimal" Hidden="true" ExternalAccess="Read/Write"/>
<Member Name="PMM_Communication_Fault" DataType="BIT" Dimension="0" Radix="Decimal" Hidden="false" Target="ZZZZZZZZZZUDT_ALARMS0" BitNumber="0" ExternalAccess="Read/Write">
<Description>
<![CDATA[PMM Communication Fault]]>
</Description>
</Member>
<Member Name="PMM_Fault" DataType="BIT" Dimension="0" Radix="Decimal" Hidden="false" Target="ZZZZZZZZZZUDT_ALARMS0" BitNumber="1" ExternalAccess="Read/Write"/>
</Members>
</DataType>
<DataType Name="UDT_HMI_PMM" Family="NoFamily" Class="User">
<Members>
<Member Name="STATE" DataType="DINT" Dimension="0" Radix="Decimal" Hidden="false" ExternalAccess="Read/Write"/>
<Member Name="PMM_Total_Power" DataType="REAL" Dimension="0" Radix="Float" Hidden="false" ExternalAccess="Read/Write">
<Description>
<![CDATA[Current total real power usage in kilowatts (kW)]]>
</Description>
</Member>
<Member Name="PMM_KWH_Consumed" DataType="REAL" Dimension="0" Radix="Float" Hidden="false" ExternalAccess="Read/Write">
<Description>
<![CDATA[Total energy consumed over time in kilowatt-hours (kWh)]]>
</Description>
</Member>
<Member Name="PMM_Max_Total_Power" DataType="REAL" Dimension="0" Radix="Float" Hidden="false" ExternalAccess="Read/Write">
<Description>
<![CDATA[Highest recorded real power usage in kilowatts (kW)]]>
</Description>
</Member>
<Member Name="Alarm" DataType="UDT_ALARMS_PMM" Dimension="0" Radix="NullType" Hidden="false" ExternalAccess="Read/Write"/>
</Members>
<Dependencies>
<Dependency Type="DataType" Name="UDT_ALARMS_PMM"/>
</Dependencies>
</DataType>
</DataTypes>
<AddOnInstructionDefinitions Use="Context">
<AddOnInstructionDefinition Use="Target" Name="AOI_PMM" Class="Standard" Revision="1.0" ExecutePrescan="false" ExecutePostscan="false" ExecuteEnableInFalse="false" CreatedDate="2025-07-15T11:44:04.434Z" CreatedBy="LCIBATUMI\guga.kakhadze" EditedDate="2025-07-18T14:50:08.259Z" EditedBy="LCIBATUMI\ilia.gurielidze"
SoftwareRevision="v36.00">
<Parameters>
<Parameter Name="EnableIn" TagType="Base" DataType="BOOL" Usage="Input" Radix="Decimal" Required="false" Visible="false" ExternalAccess="Read Only">
<Description>
<![CDATA[Enable Input - System Defined Parameter]]>
</Description>
</Parameter>
<Parameter Name="EnableOut" TagType="Base" DataType="BOOL" Usage="Output" Radix="Decimal" Required="false" Visible="false" ExternalAccess="Read Only">
<Description>
<![CDATA[Enable Output - System Defined Parameter]]>
</Description>
</Parameter>
<Parameter Name="PMM_Input1" TagType="Base" DataType="AB:1420_V2_ENT_BC244CBD:I:0" Usage="InOut" Required="true" Visible="true" Constant="false"/>
<Parameter Name="PMM_Input2" TagType="Base" DataType="AB:1420_V2_ENT_A691F258:I:0" Usage="InOut" Required="true" Visible="true" Constant="false"/>
<Parameter Name="PMM_Input3" TagType="Base" DataType="AB:1420_V2_ENT_BC1E731C:I:0" Usage="InOut" Required="true" Visible="true" Constant="false"/>
<Parameter Name="PMM_Input4" TagType="Base" DataType="AB:1420_V2_ENT_922708DF:I:0" Usage="InOut" Required="true" Visible="true" Constant="false"/>
<Parameter Name="Parent_Comm_Fault" TagType="Base" DataType="BOOL" Usage="Input" Radix="Decimal" Required="true" Visible="true" ExternalAccess="Read/Write">
<DefaultData Format="L5K">
<![CDATA[0]]>
</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
<Parameter Name="PMM_Fault_I" TagType="Base" DataType="BOOL" Usage="Input" Radix="Decimal" Required="true" Visible="true" ExternalAccess="Read/Write">
<DefaultData Format="L5K">
<![CDATA[0]]>
</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
</Parameters>
<LocalTags>
<LocalTag Name="HMI" DataType="UDT_HMI_PMM" ExternalAccess="None">
<DefaultData Format="L5K">
<![CDATA[[0,0.00000000e+000,0.00000000e+000,0.00000000e+000,[0]]]]>
</DefaultData>
<DefaultData Format="Decorated">
<Structure DataType="UDT_HMI_PMM">
<DataValueMember Name="STATE" DataType="DINT" Radix="Decimal" Value="0"/>
<DataValueMember Name="PMM_Total_Power" DataType="REAL" Radix="Float" Value="0.0"/>
<DataValueMember Name="PMM_KWH_Consumed" DataType="REAL" Radix="Float" Value="0.0"/>
<DataValueMember Name="PMM_Max_Total_Power" DataType="REAL" Radix="Float" Value="0.0"/>
<StructureMember Name="Alarm" DataType="UDT_ALARMS_PMM">
<DataValueMember Name="PMM_Communication_Fault" DataType="BOOL" Value="0"/>
<DataValueMember Name="PMM_Fault" DataType="BOOL" Value="0"/>
</StructureMember>
</Structure>
</DefaultData>
</LocalTag>
<LocalTag Name="Communication_Fault" DataType="BOOL" Radix="Decimal" ExternalAccess="None">
<Description>
<![CDATA[Communication Faulted]]>
</Description>
<DefaultData Format="L5K">
<![CDATA[0]]>
</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
</LocalTags>
<Routines>
<Routine Name="Logic" Type="RLL">
<RLLContent>
<Rung Number="0" Type="N">
<Text>
<![CDATA[[XIC(PMM_Input1.ConnectionFaulted) ,XIC(Parent_Comm_Fault) ]OTE(Communication_Fault);]]>
</Text>
</Rung>
<Rung Number="1" Type="N">
<Text>
<![CDATA[[XIO(Communication_Fault) ,XIO(PMM_Fault_I) ]MOVE(PMM_Input2.TotalRealPower,HMI.PMM_Total_Power)MOVE(PMM_Input3.kWhConsumed,HMI.PMM_KWH_Consumed)MOVE(PMM_Input4.MaxTotalRealPwr,HMI.PMM_Max_Total_Power);]]>
</Text>
</Rung>
<Rung Number="2" Type="N">
<Comment>
<![CDATA[Running
]]>
</Comment>
<Text>
<![CDATA[XIO(Communication_Fault)MOVE(0,HMI.STATE);]]>
</Text>
</Rung>
<Rung Number="3" Type="N">
<Comment>
<![CDATA[Communication Faulted
]]>
</Comment>
<Text>
<![CDATA[XIC(Communication_Fault)MOVE(1,HMI.STATE);]]>
</Text>
</Rung>
<Rung Number="4" Type="N">
<Text>
<![CDATA[XIC(Communication_Fault)XIO(Parent_Comm_Fault)OTE(HMI.Alarm.PMM_Communication_Fault);]]>
</Text>
</Rung>
<Rung Number="5" Type="N">
<Text>
<![CDATA[XIO(Communication_Fault)XIO(Parent_Comm_Fault)OTE(HMI.Alarm.PMM_Fault);]]>
</Text>
</Rung>
</RLLContent>
</Routine>
</Routines>
<Dependencies>
<Dependency Type="DataType" Name="UDT_HMI_PMM"/>
</Dependencies>
</AddOnInstructionDefinition>
</AddOnInstructionDefinitions>
</Controller>
</RSLogix5000Content>